What is the Tan Delta Test?
Hengfeng supply professional and honest service.
A pure insulator when is connected across line and earth behaves as a capacitor. In an ideal insulator, as the insulating material which acts as dielectric too, is 100 % pure, the electric current passing through the insulator, only have a capacitive component. There is no resistive component of the current, flowing from line to earth through the insulator as in ideal insulating material, there is zero per cent impurity.
In a pure capacitor, the capacitive electric current leads the applied voltage by 90o.
In practice, the insulator cannot be made 100% pure. Also due to the aging of insulators, the impurities like dirt and moisture enter into them. These impurities provide the conductive path to the current. Consequently, an electric leakage current flowing from line to earth through the insulator has a resistive component.
Hence, it is needless to say that, for a good insulator, this resistive component of the electric leakage current is quite low. In another way, the healthiness of an electrical insulator can be determined by the ratio of the resistive component to the capacitive component. For a good insulator, this ratio would be quite low. This ratio is commonly known as tanδ or tan delta.
Sometimes it is also referred to as the dissipation factor.
Thus, tan δ = IR/ IC
NB: This δ angle is known as the loss angle.
On which instruments Tan Delta testing can be done?
Tan δ testing can be done on various power types of equipment used in substations like transformers, winding, current transformer, potential transformer, transformer bushing, cables, generators. It is performed to assess the quality of insulation and is performed in combination with various test likeTTR, WRM, etc.
Reasons for doing Tan δ testing?
The main purpose of the tan delta test is to make sure of maintaining a secure and reliable functioning of the transformer. The calculation of dissipation factor and capacitance values provides the result of insulation behavior of bushings and in windings too.
Variation in the capacitance value, for instance, indicates partial kind of breakdowns in bushings and automated movement of windings. Insulation deprivation, aging of the equipment, enhancement in the energy levels is transformed into heat. The amount of losses in these is calculated as the dissipation factor.
With the tan delta testing method, one can easily know the dissipation factor and the capacitance values at the required level of frequencies. So, any kind of aging factor can be identified earlier and the corresponding action can be implemented.
As we know that Transformers plays a very crucial part in power, so, first of all, will discuss Tan Delta Testing in Transformers.
KPM's Tan Delta Test Set (KPM - TD12)
The below process explains the method of tan delta testing in a step-by-step manner
Want more information on 240V AC Tan Delta Tester? Feel free to contact us.
The requirements necessary for this test such as cable, potential transformer, bushings, current transformer, and winding on which this testing is conducted has to be initially separated from the system.
The minimal frequency level of test voltage is applied along with the equipment where the insulation to be analyzed.
At first, normal voltage levels are applied. When the tan delta values are as expected at this voltage level, then the applied voltage level is increased by 2 times as of applied voltage.
The values of the tan delta are recorded by the tan delta controller.
To the tan delta calculating component, a loss angle analyzer is connected which compares tan delta values at higher and general voltage levels and delivers accurate results.
It has to be noted that the testing procedure to be carried out at very minimal frequency levels.
It is more recommended to conduct testing at minimal frequency levels, because when the applied voltage level is more, then the capacitive reactance of the insulator device reaches very minimal, therefore the capacitive element of the current reaches more. As the resistive element is practically constant; it is based on the applied voltage level and the insulators conductivity value.
Whereas at increased frequency level the capacitive current, is more, and then the amplitude of the vector amount of both the capacitive and resistive elements of the current reaches very high. So, the necessary level of power for the tan delta test would become more that seems to be not acceptable. Because of this, the power constraint for dissipation factor analysis, very minimal frequency test voltage is required.
KPM SC 100pf is a standard capacitor for calibration of KPM TD12
When it comes to the tan delta test, there are essentially three modes of power factor testing. Those are
GST Guard This calculates the amount of current leakage to the ground. This method eliminates the current leakage through red or blue leads. Whereas in UST, the ground is termed to be guard because grounded edges are not calculated. When the UST method is applied to the device, then the current measurement is only through blue or red leads. The current flow through the ground lead gets automatically bypassed to the AC source and thus excluded from the calculation.
UST Mode This is employed for the calculation of insulation in between ungrounded leads of the equipment. Here the individual portion of isolation has to be separated and analyze it having no other insulation connected to it.
GST Mode In this final mode of operation, both the leakage pathways are calculated by the test apparatus. The current, capacitance values, UST, and GST guards, loss in watts need to be equal to the GST test parameters. This provides the entire behavior of the test.
When the summing value of GST Guard and UST is not equal to the GST parameters, then it can be known that there is some crashing in the test set, or might the test terminal are not correctly designed.
On the whole, this is a detailed explanation of the Tan Delta Test. Here, in this article, we are completely aware of what is a tan delta test, its principle, its purpose, its methods, and its testing technique.
The smallest VLF/DC unit on the market now includes an integrated Tan Delta measurement system to perform advanced electrical insulation diagnostics. For example, this can be extremely useful when performing advanced diagnostics on cable systems as it provides valuable information as to the condition of the cable insulation and shield.
The instrument automatically performs a TD test, stepping up the voltage at the user prescribed levels (according to the IEEE) and stores the results. All test parameters including insulation resistance, capacitance, RMS current and voltage, test durations, voltage steps, tan delta, and standard deviation are all measured and displayed by the HVA28 LCD display or stored to an internal memory. Learn more about Tan Delta Diagnostics here.
The company is the world’s best 260V AC Tan Delta Tester supplier. We are your one-stop shop for all needs. Our staff are highly-specialized and will help you find the product you need.